B809A MAINTENANCE UPDATES
MODIFICATION DATE: 03/02/00 |
| 1. Check unit for wire chaffing especially around the generator especially during the first 100 hours of operation. |
| 2. Do not depress the reset pushbutton more than twice when the AC voltmeter is reading more than 150VAC. |
| 3. During starting in cold temperatures some units may trip on AC under frequency. Re- adjust the under-frequency trip setting to 370HZ. Turning the Under frequency potentiometer, located on the AC Board, counterclockwise approximately two turns will lower the trip setting. |
| 4. Loose connections may exist on the aux contact of K1 and K3 especially from unit S/Ns 1-100. Lock-tight should be applied to all the #6 Screws on the aux contactors. |
| 5. Yes the fault lights and gauges are concealed behind the panel. Some users have made a cut-out with a plexi-glass insert to allow viewing of the fault lights and gauges. Coat the plexi-glass or any type of viewing window with UV protection. |
| 6. The voltage adjust pot (VA) may get wet if the control panel door is left open in the rain. This may cause an overvoltage condition. A possible solution is to seal the pot with RTV around the stem. |